MI series heating cables - HAx (twin conductor, 300V)
MI series heating cables - HAx (twin conductor, 300V)
MI series heating cables - HAx (twin conductor, 300V) is a product line in the mineral insulated (mi) series resistance heating cables category. 23 variants are available, including HAF2M59K, HAF2M36K, HAF2M29.5K, HAF2M24.5K, HAA2M19.7K, HAA2M13.2K, HAA2M10.4K, HAA2M9000. We will help you select the right type for your installation, prepare a quotation and take care of supply and installation.
23 variants in this line
Not sure which heating cable to choose?
Tell us about your installation: the medium, pipe diameter and length, maintain temperature and operating conditions. We will select the cable, output and installation method and, if needed, prepare the design.
Product types and technical specification
| Symbol | Description | Manufacturer no. | Datasheets |
|---|---|---|---|
| HAF2M59K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 59000 Ω/km, ATEX | 32SF1180 | |
| HAF2M36K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 36000 Ω/km, ATEX | 32SF1110 | |
| HAF2M29.5K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 29500 Ω/km, ATEX | 32SF2900 | |
| HAF2M24.5K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 24500 Ω/km, ATEX | 32SF2750 | |
| HAA2M19.7K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 19700 Ω/km, ATEX | 32SA2600 | |
| HAA2M13.2K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 13200 Ω/km, ATEX | 32SA2400 | |
| HAA2M10.4K | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 10400 Ω/km, ATEX | 32SA2318 | |
| HAA2M9000 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 9000 Ω/km, ATEX | 32SA2275 | |
| HAA2M6600 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 6600 Ω/km, ATEX | 32SA2200 | |
| HAA2M5600 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 5600 Ω/km, ATEX | 32SA2170 | |
| HAB2M3750 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 3750 Ω/km, ATEX | 32SB2114 | |
| HAB2M3000 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 3000 Ω/km, ATEX | 32SB3914 | |
| HAB2M2300 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 2300 Ω/km, ATEX | 32SB3700 | |
| HAQ2M1560 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 1560 Ω/km, ATEX | 32SQ3472 | |
| HAQ2M1240 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 1240 Ω/km, ATEX | 32SQ3374 | |
| HAQ2M965 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 965 Ω/km, ATEX | 32SQ3293 | |
| HAQ2M660 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 660 Ω/km, ATEX | 32SQ3200 | |
| HAQ2M495 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 495 Ω/km, ATEX | 32SQ3150 | |
| HAQ2M330 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 330 Ω/km, ATEX | 32SQ3100 | |
| HAP2M240 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 240 Ω/km, ATEX | 32SP4734 | |
| HAP2M190 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 190 Ω/km, ATEX | 32SP4583 | |
| HAP2M150 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 150 Ω/km, ATEX | 32SP4458 | |
| HAC2M105 | MI series heating cable with Alloy 825 sheath (twin conductor, 300V), 105 Ω/km, ATEX | 32SC4324 |
What HAx2M twin-conductor MI cables are used for
HAx2M is the twin-conductor version of the Raychem HAx line for lower supply voltages. The cable is mineral insulated with an Alloy 825 sheath, and both heating conductors run inside one sheath. This allows the circuit to be powered from one end, which according to the datasheet can significantly reduce installation costs and simplify installation, especially on small-diameter pipes and impulse line routes. The line suits shorter, high-resistance circuits, such as instrumentation and short sections of industrial pipework.
Technical data
- Sheath: Alloy 825; two heating conductors
- Voltage U0/U: 300/300 V (per datasheet); typical heat output up to 200 W/m
- Max. temperature: 550°C (brazed terminations), 600°C (laser welded)
- Nominal resistance: from 105 to 59,000 Ω/km at 20°C
- Outer diameter: 3.7-4.8 mm, the smallest in the HAx family
- Ex Zones 1, 2, 21, 22; temperature class T6...T1
How to read the product code, e.g. HAQ2M660
HA stands for a heating cable with an Alloy 825 sheath, the third letter (F, A, B, Q, P or C) for the conductor material, the digit 2 for twin-conductor construction and M for the 300 V version. The final number is the resistance in Ω/km, with K meaning thousands: HAF2M59K has 59,000 Ω/km, HAC2M105 has 105 Ω/km. Catalogue numbers for this version start with 32S.
Selection and installation
High resistance at 300 V means HAx2M suits short circuits with high output per metre. We calculate the element length, resistance and sheath temperature separately for each circuit. The datasheet recommends the LS28A twin-conductor cold lead with Alloy 825 sheath (300 V, 28 A, M25 gland), described on the Alloy 825 cold leads page. For higher voltages, use the HAx twin-conductor 600 V version. OWITERM handles selection, design, supply, installation, commissioning and service.
Not sure which heating cable to choose?
Tell us about your installation: the medium, pipe diameter and length, maintain temperature and operating conditions. We will select the cable, output and installation method and, if needed, prepare the design.
Frequently asked questions
What voltage is HAx2M rated for?
+
The datasheet gives a U0/U voltage of 300/300 V for HAx2M and a typical output of up to 200 W/m. We confirm the circuit supply voltage at the design stage.
Why choose a twin-conductor cable?
+
Both conductors are in one sheath, so the circuit is powered from one end without routing the cable back. This simplifies installation on small pipes and impulse line routes.