Temperature sensors (RTD)
Temperature sensors (RTD) is a product line in the temperature sensors category. 8 variants are available: MONI-PT100-NH, MONI-PT100-EXE, MONI-PT100-EXE-AMB, MONI-PT100-EXE-SENSOR, MONI-PT100-260/2, MONI-PT100-260/5, MONI-PT100-260/10, MONI-PT100-4/20MA. We will help you select the right type for your installation, prepare a quotation and take care of supply and installation.
8 variants in this line
Not sure which control system to choose?
Tell us how many circuits you need to supply and how control should work: thermostat, controller or integration with a DCS/BMS. We will select the controls and design the control panel.
Product types and technical specification
| Symbol | Description | Manufacturer no. | Datasheets |
|---|---|---|---|
| MONI-PT100-NH | Pt100 temperature sensor with junction box, non-hazardous area | 140910-000 | No datasheetNo PDF |
| MONI-PT100-EXE | Pt100 temperature sensor with junction box, ATEX | 967094-000 | |
| MONI-PT100-EXE-AMB | Ambient temperature sensor with junction box, for hazardous areas | 1244-004451 | No datasheetNo PDF |
| MONI-PT100-EXE-SENSOR | Pt100 temperature sensor without junction box, ATEX | 529022-000 | |
| MONI-PT100-260/2 | Temperature sensor with high-temperature cable and M16 cable gland, Pt100 | 1244-006615 | No datasheetNo PDF |
| MONI-PT100-260/5 | Temperature sensor with 5 m high-temperature cable and M16 cable gland, Pt100 | 1244-020817 | No datasheetNo PDF |
| MONI-PT100-260/10 | Temperature sensor with 10 m high-temperature cable and M16 cable gland, Pt100 | 1244-020816 | No datasheetNo PDF |
| MONI-PT100-4/20MA | Pt100 temperature sensor with junction box and 4-20mA transmitter, ATEX | 704058-000 | No datasheetNo PDF |
What MONI-PT100 sensors are used for
An RTD sensor is the eye of the control system: it measures the temperature of the pipe, tank or ambient air and passes it to the controller, which switches the heating circuit. Its location determines whether the system holds the required process temperature without heating unnecessarily. Sensors from the MONI-PT100 family work with Raychem electronic temperature controllers, including NGC-40, Elexant 4010i/4020i and Elexant 5010i, which support RTD inputs. ATEX versions are suitable for Zones 1 and 2 (gas) and 21 and 22 (dust).
Variants and designations
- MONI-PT100-NH - Pt100 sensor with junction box for non-hazardous areas.
- MONI-PT100-EXE - Pt100 sensor with glass-fibre reinforced polyester box, ATEX.
- MONI-PT100-EXE-SENSOR - the same sensor without the box, with a brass M16 gland for screwing into e.g. a controller enclosure.
- MONI-PT100-EXE-AMB - ambient temperature sensor with box, for hazardous areas.
- MONI-PT100-260/2, MONI-PT100-260/5, MONI-PT100-260/10 - sensors with high-temperature cable and M16 entry; the number after the slash is the cable length in metres. According to the Elexant 450c controller datasheet, the 260/2 version operates from -50°C to +260°C (sheath Ø6 mm, 50 mm).
- MONI-PT100-4/20MA - sensor with box and 4-20 mA transmitter, ATEX, for DCS/PLC systems.
MONI-PT100-EXE and -EXE-SENSOR data
- 3-wire Pt100, DIN IEC 751, class B, stainless steel sheath.
- Measuring range -100°C to +500°C, max. sensor operating temperature +585°C.
- Length 2 m, diameter approx. 3 mm, lead bending radius 20 mm (the tip must not be bent).
- -EXE box: IP66, 4 spring terminals 0.5-2.5 mm², M20 gland for 10-14 mm cable, temperature class T6.
Selection and installation
The sensor is installed under the thermal insulation on the pipe, away from the heating cable and pipe supports, at a point representative of the whole circuit. For mounting the MONI-PT100-EXE box on the pipe, the datasheet specifies the JB-SB-26 bracket from the mounting brackets line. We define measuring points in the pipe heat tracing design, supply the sensors and connect them to the control system during commissioning. Ask us via the contact page.
Not sure which control system to choose?
Tell us how many circuits you need to supply and how control should work: thermostat, controller or integration with a DCS/BMS. We will select the controls and design the control panel.
Frequently asked questions
How does MONI-PT100-EXE differ from MONI-PT100-EXE-SENSOR?
+
Both have the same class B Pt100 measuring element, 2 m long, with a range of -100°C to +500°C. The -EXE version has its own junction box with terminals, while -EXE-SENSOR has only an M16 gland and is connected directly to an enclosure with terminals, e.g. a controller.
When is MONI-PT100-4/20MA needed?
+
When the temperature signal must reach the plant control system as a standard 4-20 mA current signal instead of a direct Pt100 resistance measurement. The transmitter is built into the sensor box.