NGC-40 prefabricated control panels

NGC-40 prefabricated control panels

NGC-40 prefabricated control panels is a product line in the heat tracing control panels category. 23 variants are available, including PSS-160A/10KA-PDS-40-24HTC/16A-T, PSS-160A/10KA-PDS-40-24HTC/16A, PSS-160A/10KA-PDS-40-30HTC/16A-T, PSS-160A/10KA-PDS-40-30HTC/16A, PSS-160A/10kA-PDS-40-12HTC/25A-2HTC3/40A-T, PSS-160A/10KA-PDS-40-12HTC/25A-2HTC3/40A, PSS-250A/25KA-T, PSS-250A/25KA. We will help you select the right type for your installation, prepare a quotation and take care of supply and installation.

23 variants in this line

Not sure which control system to choose?

Tell us how many circuits you need to supply and how control should work: thermostat, controller or integration with a DCS/BMS. We will select the controls and design the control panel.

Help me select the controls

Product types and technical specification

SymbolDescriptionManufacturer no.Datasheets
PSS-160A/10KA-PDS-40-24HTC/16A-TSupply: main switch 160A, 3P+N, 10kA. Outputs: 24 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 16A/30mA.1244-014348No PDF
PSS-160A/10KA-PDS-40-24HTC/16ASupply: main switch 160A, 3P+N, 10kA. Outputs: 24 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 16A/30mA.1244-014349No PDF
PSS-160A/10KA-PDS-40-30HTC/16A-TSupply: main switch 160A, 3P+N, 10kA. Outputs: 30 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 16A/30mA.1244-014350No PDF
PSS-160A/10KA-PDS-40-30HTC/16ASupply: main switch 160A, 3P+N, 10kA. Outputs: 30 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 16A/30mA.1244-014351No PDF
PSS-160A/10kA-PDS-40-12HTC/25A-2HTC3/40A-TSupply: main switch 160A, 3P+N, 10kA. Outputs: 12 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 16A/30mA - 2 * controller1244-014352No PDF
PSS-160A/10KA-PDS-40-12HTC/25A-2HTC3/40ASupply: main switch 160A, 3P+N, 10kA. Outputs: 12 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 16A/30mA - 2 * controller1244-014353No PDF
PSS-250A/25KA-TSupply: main switch 250A, 3P+N, 25kA. Dim.: 600 (W) * 2200 (H) * 400 (D) with plinth + Touch1500 user interface1244-014354No PDF
PSS-250A/25KASupply: main switch 250A, 3P+N, 25kA. Dim.: 600 (W) * 2200 (H) * 400 (D) with plinth1244-014355No PDF
PSS-400A/25KA-TSupply: main switch 400A, 3P+N, 25kA. Dim.: 600 (W) * 2200 (H) * 400 (D) with plinth + Touch1500 user interface1244-014356No PDF
PSS-400A/25KASupply: main switch 400A, 3P+N, 25kA. Dim.: 600 (W) * 2200 (H) * 400 (D) with plinth1244-014357No PDF
PDS-40L-18HTC/25AOutputs: 18 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 25A/30mA. Dim.: 800 (W) * 2200 (H) * 400 (D) with plinth1244-014358No PDF
PDS-40R-18HTC/25AOutputs: 18 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 25A/30mA. Dim.: 800 (W) * 2200 (H) * 400 (D) with plinth1244-014359No PDF
PDS-40L-24HTC/25AOutputs: 24 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 25A/30mA. Dim.: 1200 (W) * 2200 (H) * 400 (D) with plinth1244-014360No PDF
PDS-40R-24HTC/25AOutputs: 24 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 25A/30mA. Dim.: 1200 (W) * 2200 (H) * 400 (D) with plinth1244-014361No PDF
PDS-40L-30HTC/25AOutputs: 30 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 25A/30mA. Dim.: 1200 (W) * 2200 (H) * 400 (D) with plinth1244-014362No PDF
PDS-40R-30HTC/25AOutputs: 30 * 1-phase controller, electromechanical relays 2P (EMR), RCD 2P 25A/30mA. Dim.: 1200 (W) * 2200 (H) * 400 (D) with plinth1244-014363No PDF
PDS-40L-12HTC3/40AOutputs: 12 * 3-phase controller, electromechanical relays 4P (EMR), RCD 4P 40A/30mA. Dim.: 800 (W) * 2200 (H) * 400 (D) with plinth1244-014364No PDF
PDS-40R-12HTC3/40AOutputs: 12 * 3-phase controller, electromechanical relays 4P (EMR), RCD 4P 40A/30mA. Dim.: 800 (W) * 2200 (H) * 400 (D) with plinth1244-014365No PDF
PDS-40-12SLIMOutputs: 12 * 3-phase NGC-40-SLIM temperature limiter, electromechanical contactors 4P 40A (EMR), up to 3 temperature sensors per limiter1244-014476No PDF
PDS-40L-3PASC-24CB/25AOutputs: 3 PASC groups, 3 * electromechanical contactor 4P 80A (EMR), 24 * RCD 2P 25A/30mA. Dim.: 800 (W) * 2200 (H) * 400 (D) with plinth1244-014477No PDF
PDS-40R-3PASC-24CB/25AOutputs: 3 PASC groups, 3 * electromechanical contactor 4P 80A (EMR), 24 * RCD 2P 25A/30mA. Dim.: 800 (W) * 2200 (H) * 400 (D) with plinth1244-014478No PDF
PDS-L-30CB/25AOutputs: 30 * RCD 2P 25A/30mA + auxiliary contacts, without controllers (left-hand version)1244-014479No PDF
PDS-R-30CB/25AOutputs: 30 * RCD 2P 25A/30mA + auxiliary contacts, without controllers (right-hand version)1244-014480No PDF

What NGC 40 prefabricated panels are used for

The NGC 40 panel combines power distribution, protection and control of all the heating circuits of an installation in a single cabinet. In the HTC sections each output has its own NGC-40 controller and a 30 mA RCBO, so the system itself monitors temperature, current and earth leakage on every circuit. The prefabricated configuration shortens cabinet design and assembly compared with a panel built from scratch, and sensor signals and alarms are sent to a Touch 1500 panel or a supervisory system. The power circuits for the heating cables in the field are fed from the cabinet.

Variants and designations

  • PSS - incoming power section with a 3P+N main switch: PSS-160A/10KA, PSS-250A/25KA, PSS-400A/25KA; the number after the slash is the short-circuit breaking capacity (10 or 25 kA).
  • PSS-160A/10KA-PDS-40-24HTC/16A and -30HTC/16A - complete sets: incoming power section with 24 or 30 single-phase controllers and 2P 16A/30mA breakers.
  • PSS-160A/10KA-PDS-40-12HTC/25A-2HTC3/40A - mixed set: 12 single-phase circuits and 2 three-phase circuits.
  • Suffix -T - version with a Touch 1500 user interface.
  • PDS-40L/-40R-18HTC, -24HTC, -30HTC/25A - outgoing sections with 18, 24 or 30 single-phase controllers and 2P 25A/30mA breakers; L and R denote the left- and right-hand versions.
  • PDS-40L/R-12HTC3/40A - 12 three-phase controllers, 4P 40A/30mA breakers.
  • PDS-40-12SLIM - 12 NGC-40-SLIM temperature limiters, up to 3 sensors per limiter.
  • PDS-40L/R-3PASC-24CB/25A - 3 groups controlled by the PASC algorithm; PDS-L/R-30CB/25A - 30 breakers without controllers.

Dimensions and construction

According to the product descriptions, the cabinets are 2200 mm high and 400 mm deep including the plinth; the width is 600 mm for the PSS-250A and PSS-400A sections, 800 mm for sections with 18 single-phase or 12 three-phase controllers, and 1200 mm for sections with 24 and 30 controllers. The output relays are electromechanical (EMR).

Selection and installation

We determine the configuration from the power balance of all circuits: the number of single- and three-phase circuits, the start-up currents of the self-regulating cables, the limiters required and the method of communication with the DCS. We supply the cabinet, run the cabling to the circuits, configure the controllers and commission the system. Elexant 9200i wireless modules and accessories can be found in the heat tracing control panels category. Send us your circuit schedule via the contact page.

Not sure which control system to choose?

Tell us how many circuits you need to supply and how control should work: thermostat, controller or integration with a DCS/BMS. We will select the controls and design the control panel.

Help me select the controls

Frequently asked questions

What do the letters L and R mean in PDS-40L and PDS-40R?

+

They are the left- and right-hand versions of the same outgoing section. The choice of side depends on how the outgoing sections are to be lined up with the PSS incoming power section in the cabinet suite.

What is the difference between PSS-160A/10KA-PDS-40-24HTC/16A and the -T version?

+

Both contain a 160 A incoming power section and 24 single-phase controllers. The version with the -T suffix is additionally fitted with a Touch 1500 operator panel for operating and monitoring the NGC-40 system.